# What is RAGAGEP (recognized and generally accepted good engineering practice)?

> RAGAGEP, recognized and generally accepted good engineering practice, is the US process safety benchmark for equipment design, inspection and testing. The Occupational Safety and Health Administration (OSHA) process safety standard, 29 CFR 1910.119, and the Environmental Protection Agency (EPA) Risk Management Program rule both use it. Employers choose the applicable codes, standards or internal practices and document compliance.

- Label: Fact
- Type: Explainer
- Published: 2026-11-14T12:02:06+09:00
- By: Jun Zhong
- Researched and drafted by: Beacon's AI newsroom
- Checked by: Jun Zhong on 2026-11-14
- Topics: LNG, Refining
- Canonical: https://beacon.winda.ai/library/ragagep/

## Why does it matter?

Adopting a recommended practice does not mean picking which of its clauses to follow. In its 2016 enforcement memorandum, OSHA says that when an employer departs from a "shall" statement in the RAGAGEP it has adopted, OSHA presumes a violation, and the employer can then explain why its approach is still good engineering practice [2]. Departing from a "should" statement is not presumed a violation, as long as the equipment is still documented as compliant [2]. In refinery inspections under a national emphasis program that began in June 2007, OSHA issued many citations tied to RAGAGEP, including insufficient thickness measurements and inspection frequencies that were unacceptable or never set [3].

## Where does RAGAGEP appear in the rules?

| Provision | What it requires |
|---|---|
| 29 CFR 1910.119(d)(3)(ii) | Document that equipment complies with RAGAGEP [1] |
| 29 CFR 1910.119(d)(3)(iii) | For equipment built to codes no longer in general use, determine and document that it is designed, maintained, inspected, tested and operated safely [1] |
| 29 CFR 1910.119(j)(4)(ii) | Inspection and test procedures follow RAGAGEP [1] |
| 29 CFR 1910.119(j)(4)(iii) | Inspection and test frequency follows manufacturers' recommendations and good engineering practice, and tightens when operating experience shows the need [1] |
| 40 CFR 68.65(d)(2) and (3); 68.73(d)(2) and (3) | The same duties for EPA Program 3 processes [4][6] |
| 40 CFR 68.67(c)(10), added in 2024 | Process hazard analyses address gaps between the codes a process was built to and their current versions [5] |

In OSHA's reading, the term governs three things: how equipment is designed and maintained, how it is inspected and tested, and how often [2].

## What counts as RAGAGEP?

OSHA's memo lists these sources and says they are not ranked [2]:

- **Widely adopted codes,** such as fire and electrical codes that state and local governments adopt. [2]
- **Consensus documents** developed under American National Standards Institute (ANSI) due-process rules, such as the ASME B31.3 process piping code. [2]
- **Non-consensus documents** that an industry widely accepts, such as Chlorine Institute pamphlets. [2]
- **Manufacturers' recommendations.** [2]
- **Internal standards,** provided they themselves represent recognized and generally accepted practice. [2]

OSHA's 2017 refinery guidance names API 510, API 570 and API 580 as examples of inspection RAGAGEP [3]. More than one document can apply: OSHA accepts either API RP 520 Part II or ISO 4126-9 for relief valve installation [2]. Mixing selected clauses from several documents may leave hazards uncontrolled, and applying a document outside its intended field, such as an ammonia refrigeration vessel practice in a refinery, can lead to citations [2].

## How does OSHA read shall and should in RAGAGEP?

| Language in the adopted RAGAGEP | OSHA's enforcement position |
|---|---|
| "Shall", "must", "shall not" | The developer's mandatory minimum; a deviation is presumed a violation unless the employer shows its approach is still RAGAGEP |
| "Should" | Following it is presumed acceptable; skipping it is not presumed a violation, but the inspector checks the alternative and the compliance record |
| "Should not" | Treated like "should" |
| Normative annex | Explains how to comply and may hold both "shall" and "should" |
| Informative annex | Background and references; employers are expected to read it, not to consult every source it cites |

Source: OSHA enforcement memorandum, 11 May 2016, which replaced a June 2015 version [2].

## Does a new edition apply to existing equipment?

Only if the new edition says so. OSHA states that a more protective update that is not explicitly retroactive does not oblige employers to upgrade, but paragraph (d)(3)(iii) still requires them to determine and document that the equipment operates safely [2]. OSHA also tells its inspectors to establish the equipment's age, installation date and modifications, and the edition and date of the RAGAGEP the employer selected [2].

EPA goes further in its guidance. Its frequently asked question, updated 20 April 2026, expects owners to review new and updated RAGAGEP regularly for safety gaps, and says the absence of an incident so far is not a sound reason to set aside updated practice [7]. EPA's 2024 amendments wrote this gap check into process hazard analysis at 40 CFR 68.67(c)(10) [5]. On 24 February 2026 EPA proposed removing that paragraph while keeping the duty to evaluate gaps under its safety information rules [8]. As of 25 October 2026, the eCFR text, up to date as of 22 October 2026, still contains it [5].

## Where integrity problems show up

| Requirement | What it means for integrity records or work | In the Library |
|---|---|---|
| 1910.119(d)(3)(ii), document compliance | Equipment files need the selected RAGAGEP, with edition and date, and evidence of compliance; missing documentation is itself citable [2] | [What is mechanical integrity (MI)?](/library/mechanical-integrity/) |
| 1910.119(j)(4)(ii), inspection procedures | Refinery citations included no procedure fixing the number and location of thickness readings, and rising thickness readings left uninvestigated [3] | [What are condition monitoring locations (CMLs)?](/library/condition-monitoring-locations/) |
| 1910.119(j)(4)(iii), frequency | Citations included inspection frequencies never established and corrosion rates never calculated to set intervals [3] | [How are inspection intervals set for vessels, piping and tanks?](/library/inspection-intervals/) |
| 1910.119(j)(5), deficiencies | Equipment outside limits set by process safety information, RAGAGEP included, is corrected before further use or kept safe in the interim under management of change [2] | [What is fitness-for-service (API 579-1/ASME FFS-1)?](/library/fitness-for-service/) |
| 1910.119(d)(3)(iii), older equipment | Equipment built to outdated codes needs a documented case that it is still safe [1][2] | What is asset life extension? |
| 1910.119(j)(2), written procedures | Failing to follow one's own stricter internal inspection procedures can be cited even when published RAGAGEP is met [2] | [What should an inspection plan contain?](/library/inspection-plan/) |

Sources: 29 CFR 1910.119 [1]; OSHA memorandum, 2016 [2]; OSHA 3918, 2017 [3].

## Sources

1. [29 CFR 1910.119, Process safety management of highly hazardous chemicals, eCFR, US Office of the Federal Register](https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-H/section-1910.119)
2. [RAGAGEP in Process Safety Management Enforcement (memorandum to regional administrators), US Occupational Safety and Health Administration (OSHA)](https://www.osha.gov/laws-regs/standardinterpretations/2016-05-11), 2016-05-11
3. [Process Safety Management for Petroleum Refineries: Lessons Learned from the Petroleum Refinery Process Safety Management National Emphasis Program (OSHA 3918-08), US Occupational Safety and Health Administration (OSHA)](https://www.osha.gov/Publications/OSHA3918.pdf)
4. [40 CFR 68.65, Process safety information, eCFR, US Office of the Federal Register](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-68/subpart-D/section-68.65)
5. [40 CFR 68.67, Process hazard analysis, eCFR, US Office of the Federal Register](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-68/subpart-D/section-68.67)
6. [40 CFR 68.73, Mechanical integrity, eCFR, US Office of the Federal Register](https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-68/subpart-D/section-68.73)
7. [Complying with process safety information (PSI) resulting from new and updated recognized and generally accepted good engineering practices (RAGAGEP), US Environmental Protection Agency (EPA)](https://www.epa.gov/rmp/complying-process-safety-information-psi-resulting-new-and-updated-recognized-and-generally)
8. [Accidental Release Prevention Requirements: Risk Management Programs Under the Clean Air Act; Common Sense Approach to Chemical Accident Prevention (proposed rule), 91 FR 8970, US Environmental Protection Agency, via Federal Register (govinfo)](https://www.govinfo.gov/content/pkg/FR-2026-02-24/html/2026-03633.htm), 2026-02-24

Published by Winda Beacon (https://beacon.winda.ai).