What is a safety instrumented system (SIS)?
A safety instrumented system (SIS) is an independent set of sensors, logic solvers and final elements that automatically brings a process to a safe state. For example, it closes a shutdown valve when a dangerous condition is detected. IEC 61511 is the process-industry standard for SIS; its US adoption is ANSI/ISA-84.00.01.
By Jun Zhong, Editor·Researched and drafted by Beacon's AI newsroom·Checked by Jun Zhong, Editor·Last checked ·Next review
Why does it matter?
In a UK Health and Safety Executive (HSE) analysis of 34 incidents involving control and protection systems, 44% of the primary causes were traced to an inadequate specification, before any design work, and another 20% to changes made after commissioning 1. HSE concluded that most of the failures came from defects that a systematic, risk-based approach over the system's life could have anticipated 1. At a tank terminal in Bayamón, Puerto Rico, a gasoline tank overfilled in 2009 and the vapor cloud ignited; the US Chemical Safety and Hazard Investigation Board (CSB) found that the tanks had neither an independent high-level alarm nor an independent automatic overfill prevention system 2.
What are the parts of an SIS?
HSE describes an instrumented system by its plant interface: sensors as inputs, logic elements that decide, and actuators as outputs, supported by utilities such as electric power and instrument air 3. When a system performs a safety function, every element needed for that function, utilities included, belongs to the safety-related system 3.
| Part | Job | Examples in HSE guidance |
|---|---|---|
| Sensor | Measures the process condition | Input devices on the plant 3 |
| Logic solver | Compares the reading with the trip setting and decides to act | Relays, programmable logic controllers (PLCs) or other programmable electronics 3 |
| Final element | Acts on the process | Output devices (actuators) 3; at Bayamón, the CSB called for systems that stop the transfer 2 |
| Support systems | Keep the other parts working | Electric power supplies and instrument air 3 |
The US Occupational Safety and Health Administration (OSHA) notes that the SIS covered by the US consensus standard may use electrical, electronic or programmable electronic technology 4.
How is an SIS different from the basic process control system?
The basic process control system keeps the plant within normal operating limits. Protective functions such as trips, interlocks and emergency shutdown detect the onset of a hazard and end it, keeping the plant within its safe operating limits 3. HSE advises that a control system whose failure could raise the demand on a safety system should be independent of it and separate from it 3. Common-mode failures are reduced by independence from shared utilities and management systems, and by diversity, for example a relief valve alongside the instrumented trip 3.
The CSB made the same point after Bayamón. It recommended automatic overfill prevention kept physically apart from, and independent of, the tank level gauging and control, engineered to an appropriate safety integrity level under IEC 61511, and proof tested often enough to keep that level 2.
How much protection must an SIS give?
HSE defines safety integrity as the likelihood that a safety-related system performs its function under all stated conditions when it is needed 3. A system in low demand mode is called on no more than once a year; one in high demand or continuous mode is called on more often 3. IEC 61508, the parent standard, assigns four safety integrity levels (SILs) to required risk reduction, and IEC 61511 applies IEC 61508 to the process sector 3,6.
The required level can be set from hazard and risk analysis of the equipment under control, which estimates how much risk reduction is needed 3. Methods for setting it are covered in What is layer of protection analysis (LOPA)? and What is a safety integrity level (SIL)?.
How is an SIS kept working over its life?
- Through a managed lifecycle. In HSE's description, the lifecycle starts with hazard and risk evaluation and the specification, moves through design, validation, installation and commissioning, and continues through operation, maintenance and modification 3.
- Through proof testing. The CSB recommended proof tests often enough to maintain the required integrity 2. In COMAH safety reports, HSE assessors look for sample proof test procedures, records of completed proof tests and records of staff competence 8.
- Through the US process safety rule. OSHA's mechanical integrity element covers emergency shutdown systems and controls, including sensors, alarms and interlocks, which must be inspected and tested to good engineering practice with each test recorded 7. Process safety information must list safety systems, and operating procedures must describe them and their functions 7.
- Through controlled change. HSE expects functional safety assessment records for modifications made to an SIS 8.
Where integrity problems show up
| Element or step | Integrity link | In the Library |
|---|---|---|
| Writing the safety requirements | 44% of primary causes in HSE's 34-incident analysis came from inadequate specification 1 | What is layer of protection analysis (LOPA)? |
| Keeping protection independent of control | At Bayamón the tanks lacked independent high-level alarms and overfill prevention; the CSB called for separate systems engineered to a safety integrity level 2 | What is a safety integrity level (SIL)? |
| Proof testing and keeping records | OSHA requires documented inspection and testing of shutdown systems and interlocks 7; HSE expects proof test procedures and records 8 | What is mechanical integrity (MI)? |
| Changing the system | 20% of primary causes in HSE's analysis were changes after commissioning 1; HSE expects assessment records for SIS changes 8 | What is management of change (MOC)? |
| Choosing the basis of design | OSHA considers ANSI/ISA-84.00.01-2004 recognized and generally accepted good engineering practice for SIS, though not the only one 5 | What is RAGAGEP (recognized and generally accepted good engineering practice)? |
| Listing safety-critical equipment | HSE expects COMAH safety reports to say where inventories of instrument safety-critical elements, SIS included, are kept 8 | What are safety and environmental critical elements (SECEs)? |
Sources: HSE HSG238 1; CSB Bayamón report, 2015 2; OSHA interpretation, 2005 5; 29 CFR 1910.119 7; HSE COMAH assessment criteria 8.
Common questions
- Is an SIS the same as an emergency shutdown system?
- They overlap. HSE groups trips, interlocks and emergency shutdown as protective functions distinct from process control, and OSHA's mechanical integrity element lists emergency shutdown systems and interlocked controls as covered equipment.
- Is a pressure relief valve part of an SIS?
- No. A relief valve is a mechanical device; HSE cites it as a diverse protection that does not share failure causes with instrumented systems.
- Does OSHA require IEC 61511?
- No. OSHA treats ANSI/ISA-84.00.01-2004 (IEC 61511 modified) as good engineering practice and accepts compliance with it, but does not name it as the only acceptable practice. Outside PSM coverage, OSHA has said an unsafe SIS can be cited under the General Duty Clause.
Beacon explains these concepts in its own words for education. It does not reproduce or replace the standards cited, and Winda is not affiliated with or endorsed by the organizations that publish them. Engineering decisions need the current edition of the standard and a qualified engineer.
Sources
- 1.Out of control: Why control systems go wrong and how to prevent failure, HSG238, second edition · UK Health and Safety Executive (HSE)
- 2.Final Investigation Report: Caribbean Petroleum Tank Terminal Explosion and Multiple Tank Fires, Bayamon, Puerto Rico, Report No. 2010.02.I.PR, and investigation page · US Chemical Safety and Hazard Investigation Board (CSB) ·
- 3.Control systems (COMAH technical measures) · UK Health and Safety Executive (HSE)
- 4.Compliance with PSM and ANSI/ISA-S84.01 for safety instrumented systems (standard interpretation) · US Occupational Safety and Health Administration (OSHA) ·
- 5.Use of ANSI/ISA S84.00.01-2004 Parts 1-3 (IEC 61511 MOD) to comply with OSHA's Process Safety Management standard (standard interpretation) · US Occupational Safety and Health Administration (OSHA) ·
- 6.IEC 61511-1:2016, Functional safety: Safety instrumented systems for the process industry sector, Part 1 (webstore page) (IEC 61511-1:2016 (amendment 1, 2017)) · International Electrotechnical Commission (IEC) ·
- 7.29 CFR 1910.119, Process safety management of highly hazardous chemicals, paragraphs (d), (f) and (j) · eCFR, US Office of the Federal Register
- 8.COMAH Safety Report Assessment Manual 2015, Section 12: Electrical, control and instrumentation aspects (Appendix 12B criteria) · UK Health and Safety Executive (HSE), COMAH Competent Authority