Corrosion under insulation (CUI), explained

·5 sources

Corrosion under insulation (CUI) happens when water gets through damaged cladding and insulation holds it against hot steel, so wall loss grows out of sight until a leak. This film shows where the water comes from, why heat and shutdowns matter, and how inspectors find it.

By , Editor·Researched and drafted by ·Checked by , Editor·Last checked

16:9 · 1:51 · English subtitles on YouTube · transcript below (PT1M51S) · Read the explainer

Transcript

Insulation keeps the heat in. It can also hold water against the steel, out of sight. This is corrosion under insulation, or CUI.21

Water comes from rain, deluge systems, cooling towers or condensation, and gets in wherever the cladding fails: a failed joint seal, a dent, a panel not refitted after maintenance.32

Inside, it runs to the low points. In the field, damage is often found at the six o'clock position.23

Fibrous insulation, such as mineral wool, soaks it up and holds it against the metal, with air close by.2

That is all steel needs. At an anode, iron leaves the metal and gives up electrons. They travel through the wall to a cathode, where oxygen and water consume them.25

Heat keeps it active, and shutdowns rewet the insulation. One source flags thirty to a hundred and twenty degrees Celsius; another, fifty to a hundred and seventy-five. Where they overlap, both flag the risk.23

And under the cladding, wall loss can grow unseen until a leak.1

So inspectors cut small windows where damage is most likely, or screen through the insulation with pulsed eddy current, guided waves or radiography.231

Offshore, in 2018, exhaust piping under insulation blankets was found corroded through.4

Corrosion under insulation. Read more in the Beacon Library.2

Sources

  1. 1.API RP 583, Corrosion Under Insulation and Fireproofing, Third Edition, April 2026 (publisher's scope as listed by a standards distributor) · American Petroleum Institute ·
  2. 2.Corrosion under insulation of plant and pipework, semi-permanent circular SPC/TECH/GEN/18, issued 1 March 2011 (archived copy) · UK Health and Safety Executive ·
  3. 3.Cao, Pojtanabuntoeng, Esmaily, Thomas, Brameld, Amer and Birbilis, A Review of Corrosion under Insulation: A Critical Issue in the Oil and Gas Industry, Metals 12(4), 561, 2022 · Metals (MDPI), via MIT DSpace ·
  4. 4.Safety Bulletin No. 013: Severe Corrosion Found Under Insulation · Bureau of Safety and Environmental Enforcement ·
  5. 5.Pipeline Corrosion: Final Report, Integrity Management Program, Delivery Order DTRS56-02-D-70036, November 2008 · US Pipeline and Hazardous Materials Safety Administration