What are the main types of storage tanks?

·9 sources

Short answer

The main storage tank types are fixed-roof and floating-roof tanks near atmospheric pressure, low-pressure tanks, and pressure vessels such as spheres. US federal rules set the pressure classes (29 CFR 1910.106); API 650 and API 620 cover design and construction, and API 653 covers inspection and repair of tanks in service.

By , Editor·Researched and drafted by ·Checked by , Editor·Last checked ·Next review

How are storage tanks classified?

The first split is design pressure. The US Occupational Safety and Health Administration (OSHA) calls a tank designed for up to 0.5 pounds per square inch gauge (psig), about 3.4 kPa, an atmospheric tank; one designed for more than 0.5 and up to 15 psig (about 103 kPa) a low-pressure tank; and one designed for more than 15 psig a pressure vessel (29 CFR 1910.106) 2.

Tanks are also sorted by roof, location and how they are built. Roofs are fixed or floating, as described below 1. Most tanks stand above ground; for buried tanks, the US Environmental Protection Agency (EPA) notes that the soil damps temperature swings, so vapor losses come mainly from changes in liquid level 1. EPA's spill prevention guidance separates shop-fabricated tanks, built in a factory and usually smaller with fewer welds, from field-erected tanks welded on site 4.

What are the main types of storage tank?

TypeMain featuresOSHA pressure classUsual design document
Fixed-roofSteel shell with a permanent cone, dome or flat roof; freely vented or fitted with a pressure-vacuum ventAtmosphericAPI 650
External floating roofOpen-top shell; a welded steel pontoon or double-deck roof floats on the liquid, with a rim seal against the shellAtmosphericAPI 650
Internal floating roofFixed roof over a floating deck that rests on the liquid (contact) or on pontoons above it (noncontact)AtmosphericAPI 650
Domed external floating roofExternal floating roof tank with a fixed dome added on topAtmosphericAPI 650
Horizontal tankSmall cylindrical tank of steel or fiberglass-reinforced plastic, typically under 40,000 gallons 1AtmosphericVaries
Low-pressure tankLarge field-welded tank holding liquid with gas or vapor above it, or gas aloneLow-pressureAPI 620
SphereSpherical pressure vessel for liquefied gases such as LPG and ammoniaPressure vesselASME Section VIII
Refrigerated liquefied gas tank systemLow-pressure tank system for gases kept liquid by refrigeration, with optional secondary containmentLow-pressureAPI 625

Sources: EPA AP-42 Section 7.1, September 2025 1; 29 CFR 1910.106 2; API 2025 Publications Catalog 3; NIST SP 780, 1990 7; OSHA Technical Manual, Section IV, Chapter 3 8.

Roof design is mostly about vapor losses. EPA describes fixed-roof tanks as the cheapest to build and the minimum acceptable for organic liquids; they lose vapor as the vapor space breathes with daily temperature changes and as filling pushes vapor out 1. A floating roof rides on the liquid, so its losses come mainly through rim seals and deck fittings and from liquid left on the shell as the level falls; on an open-top tank, wind drives much of the rim loss, which a dome removes 1.

Which standards and rules apply to storage tanks?

The American Petroleum Institute (API) covers most welded steel tanks 3. API 650 sets requirements for vertical, aboveground, welded carbon or stainless steel tanks at internal pressures close to atmospheric, with the whole bottom uniformly supported; API 620 covers large, field-assembled, welded low-pressure tanks; and API 625 covers refrigerated liquefied gas tank systems 3. API 2000 covers normal and emergency venting of atmospheric and low-pressure tanks 3.

For tanks in service, API 653 sets minimum requirements for inspection, repair, alteration, relocation and reconstruction of tanks built to API 650, and API RP 575 describes inspection practices for atmospheric and low-pressure tanks 3. API RP 651 covers cathodic protection of aboveground tank bottoms 3.

Federal rules depend on what the tank stores and where it sits. OSHA's flammable liquids rule lists API 650 among the standards atmospheric tanks may be built to, and API 620 for low-pressure tanks (older editions) 2, and its process safety management standard lists storage tanks among the equipment that needs a mechanical integrity program in covered processes (29 CFR 1910.119(j)(1)(i)) 9. EPA's spill prevention guidance points to API 653 and the Steel Tank Institute's SP001 as the industry standards for tank integrity testing 4. Breakout tanks on hazardous liquid pipelines fall under the pipeline rules of the Pipeline and Hazardous Materials Safety Administration (PHMSA) in 49 CFR Part 195 5.

How are storage tanks inspected?

EPA's guidance describes two levels of formal inspection under API 653 4. The in-service external inspection is a visual check against a checklist plus ultrasonic thickness readings on the shell 4. The out-of-service internal inspection, done by an API 653 certified inspector, covers the floor, welds, shell, roof and nozzles, using methods such as magnetic flux leakage floor scanning, vacuum box testing of floor welds, helium leak testing, ultrasonic readings and settlement surveys 4.

The same guidance calls for a brittle fracture evaluation of field-erected tanks after a repair, alteration, reconstruction or change in service 4. Site conditions such as age, service history and nearness to saltwater can shorten inspection schedules 4.

Where integrity problems show up

Tank partTypical integrity issueIn the Library
Bottom plates, soil sideSoil-side corrosion, including microbiologically influenced corrosion under iron oxide tuberclesWhat is soil corrosion?; What is microbiologically influenced corrosion (MIC)?
Bottom plates on a cathodically protected padProtection that does not reach the criterion leaves the underside corrodingHow does cathodic protection work?
Floor and floor weldsMetal loss and leaks found out of service by floor scanning and vacuum box testingMagnetic flux leakage
Field-erected tank shellBrittle fracture, most often at the first hydrotest, the first cold-weather filling, a change to colder service or after a repairWhat is brittle fracture?
Shell exterior near the coastFaster corrosion close to saltwaterWhat is atmospheric corrosion?
LPG spheres in wet hydrogen sulfide serviceCracking, mainly in weld heat-affected zonesWhat is wet hydrogen sulfide (H2S) damage?

Sources: EPA SPCC guidance, 2013 4; OSHA Technical Manual, Section IV, Chapter 3 8; AMPP, 2021 6. The AMPP case study described four uncoated API 650 tank bottoms at a refinery that failed by soil-side MIC between 2013 and 2015, with pitting rates of 1 to 2 mm per year and cathodic protection potentials short of the criterion in a 2016 survey 6.

Common questions

Is a storage tank a pressure vessel?
Not usually. Under OSHA's classes, a tank designed for up to 15 psig is an atmospheric or low-pressure tank, and only above 15 psig does it become a pressure vessel.
What is a breakout tank?
It is a tank on a hazardous liquid pipeline system that relieves pressure surges or receives and stores liquid for reinjection into the pipeline, and it is regulated under 49 CFR Part 195.

Beacon explains these concepts in its own words for education. It does not reproduce or replace the standards cited, and Winda is not affiliated with or endorsed by the organizations that publish them. Engineering decisions need the current edition of the standard and a qualified engineer.

Sources

  1. 1.AP-42, Fifth Edition, Volume I, Chapter 7, Section 7.1: Organic Liquid Storage Tanks · US Environmental Protection Agency (EPA)
  2. 2.29 CFR 1910.106, Flammable liquids (in 29 CFR Part 1910, Subpart H) · eCFR, US Office of the Federal Register
  3. 3.2025 Publications Catalog (Refining: Storage Tanks; Inspection of Refinery Equipment) · American Petroleum Institute (API)
  4. 4.SPCC Guidance for Regional Inspectors, Chapter 7: Inspection, Evaluation, and Testing · US Environmental Protection Agency (EPA) ·
  5. 5.49 CFR Part 195, Subpart A, General (sections 195.1 and 195.2) · eCFR, US Office of the Federal Register
  6. 6.Oil Storage Tank Failure: A MIC Case Study · Association for Materials Protection and Performance (AMPP) ·
  7. 7.NIST Special Publication 780, Guidelines for Pressure Vessel Safety Assessment (S. Yukawa) · US National Institute of Standards and Technology (NIST)
  8. 8.OSHA Technical Manual, Section IV, Chapter 3: Pressure Vessel Guidelines · US Occupational Safety and Health Administration (OSHA)
  9. 9.29 CFR 1910.119, Process safety management of highly hazardous chemicals · eCFR, US Office of the Federal Register