What is API 650 (welded steel tanks for oil storage)?

·11 sources

Short answer

API Standard 650 sets the American Petroleum Institute's minimum requirements for new vertical, aboveground, welded steel storage tanks. It covers material, design, fabrication, erection and testing for carbon or stainless steel tanks at internal pressures near atmospheric. The current edition is the 13th (March 2020). Once a tank is in service, API 653 takes over.

By , Editor·Researched and drafted by ·Checked by , Editor·Last checked ·Next review

Why does it matter?

In Chesapeake, Virginia, in 2008, a 2-million-gallon fertilizer tank split open about 3.5 inches below the fill level calculated for it, a level that assumed weld radiography never performed 3. The US Chemical Safety and Hazard Investigation Board (CSB) found that the welds on new plates replacing riveted joints did not meet accepted tank fabrication quality; two contract workers were critically injured, and at least 200,000 gallons of fertilizer were never recovered 3. A US Environmental Protection Agency (EPA) alert covering five tank ruptures from 1997 to 2008 found that all the failed tanks appeared to have defective welds 4. How tank welds are designed, made and examined, under API 650 for new tanks and API 653 for repairs, decides how much liquid a tank can safely hold.

What tanks does API 650 cover?

API's 2025 catalog describes the scope: vertical, cylindrical, aboveground tanks, open or closed top, welded from carbon or stainless steel, at internal pressures close to atmospheric 1. Higher internal pressure is allowed if extra requirements are met; the whole bottom must be uniformly supported; and tanks in non-refrigerated service are limited to a maximum design temperature of 200 °F (93 °C) 1. Refrigerated liquefied gas tanks fall under API 625 instead 1.

Federal rules separate the neighboring standards mainly by pressure 6,10:

Tank or vesselPressure range in the federal ruleConstruction standard
Small shop-welded tank, 90 to 750 barrelsAbout atmosphericAPI Spec 12F
Vertical cylindrical welded steel tankVapor space up to 2.5 pounds per square inch gauge (psig), or the pressure the roof weight producesAPI 650
Welded low-pressure tankUp to 15 psigAPI 620
Liquefied petroleum gas (LPG) tank, 2,000 gallons or moreAbove 15 psigAPI 2510
Pressure vesselAbove 15 psigAmerican Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code, Section VIII

Sources: 49 CFR 195.132(b), for pipeline breakout tanks 6; 29 CFR 1910.106(b)(1) and US National Institute of Standards and Technology (NIST) SP 780, 1990, for API 620 and Section VIII 10,11.

What does API 650 set, from material to testing?

Its minimum requirements run from the steel chosen, through design and the work done in the shop and on site, to the tests a finished tank must pass 1. EPA notes that API 650 design adds metal for expected corrosion and accounts for how dense the stored liquid is, and that radiography is applied to API 650 tanks to confirm complete penetration and fusion of welded joints; it also warns that radiography cannot reveal poor mechanical properties in a weld 4.

Testing before service is written into federal rules. Breakout tanks built to API 650 and placed in service after 2 October 2000 must be tested to the testing sections of API 650 8. The flammable liquids standard of the US Occupational Safety and Health Administration (OSHA) requires every tank to be strength tested before use, and accepts an ASME stamp, API monogram or Underwriters Laboratories label as evidence 10.

The standard dates back to 1961 3. OSHA's rule still cites the third edition of 1966, titled Welded Steel Tanks for Oil Storage; the 13th edition is titled Welded Tanks for Oil Storage 1,2,10.

Who requires API 650?

AuthorityRuleWhat it says
US Pipeline and Hazardous Materials Safety Administration (PHMSA)49 CFR 195.132(b)(3) and 195.3Breakout tanks in the API 650 pressure range, first placed in service after 2 October 2000, must be designed and built to API 650, 13th edition incorporated by reference 5,6
OSHA29 CFR 1910.106(b)(1)(iii)Atmospheric tanks for flammable liquids may be built to API 650, among other named standards 10
StatesState tank rulesSeveral states incorporate API 650 and API 653 by reference, including for liquid fertilizer, according to CSB 3
Industry guidanceFertilizer industry tank guidelinesCall for liquid fertilizer tanks to be designed and built to API 650, according to EPA 4

What happens after the tank enters service?

API 653, Tank Inspection, Repair, Alteration, and Reconstruction (5th edition, 2014, with addenda of 2018 and 2020), covers tanks built to API 650 and its predecessor, API 12C 1. Its scope runs from the foundation and bottom through the shell, roof, appurtenances and nozzles to the first flange; it governs once a tank is in service, and where as-built details are missing it calls for details giving integrity equal to the current API 650 1. For federally regulated breakout tanks, repairs and in-service inspection must follow API 653 (the rule incorporates its 2001 third edition), and bottom cathodic protection and linings follow API Recommended Practices 651 and 652 5,7,9.

Where integrity problems show up

Decision or step at this stageWhat it affects laterIn the Library
Weld quality and extent of radiographySets the fill level a tank can carry; defective welds caused the tank ruptures EPA reviewed, and in Chesapeake, Virginia, in 2008 the assumed radiography had not been done 3,4Radiographic testing
Corrosion allowance in the designMetal available to lose before thickness limits are reached; where corrosion exceeds what design formulas provide, OSHA requires extra thickness or a coating 4,10Corrosion allowance
Tank bottom protection: cathodic protection and liningsCorrosion at the base and in contact with moist ground is a known rupture risk factor; federal rules tie bottom protection for breakout tanks to API RP 651 and RP 652 4,9How does cathodic protection work?, What is soil corrosion?
First fill and hydrostatic testEPA, citing API 653, notes tanks are more likely to fail on the first fill to maximum level; the Chesapeake tank failed on its first fill after modification 3,4What is a hydrostatic test?
As-built records handed overIf the as-built records and the original standard are both silent on a detail, API 653 calls for a detail that gives integrity equal to the current API 650 1What documents are handed over when a project is completed?
Damage found in serviceAssessed with API 579-1/ASME FFS-1 fitness-for-service methods, as EPA and CSB both point to 1,3,4What is fitness-for-service (API 579-1/ASME FFS-1)?

Sources: API 2025 catalog 1; CSB, 2009 3; EPA, 2009 4; 49 CFR 195.565 and 195.579 9; 29 CFR 1910.106 10.

Common questions

What is the difference between API 650 and API 653?
They are often confused. API 650 covers building a new tank; API 653 covers inspection, repair, alteration, relocation and reconstruction after it enters service, and governs where the two conflict.
What is the difference between API 650 and API 620?
API 650 tanks operate near atmospheric pressure, while API 620 covers welded low-pressure tanks up to 15 psig.
Does API 650 cover refrigerated tanks?
No. Its scope is non-refrigerated service, and refrigerated liquefied gas tank systems are covered by API 625. See [What are the main types of storage tanks?](/library/storage-tank-types/).

Beacon explains these concepts in its own words for education. It does not reproduce or replace the standards cited, and Winda is not affiliated with or endorsed by the organizations that publish them. Engineering decisions need the current edition of the standard and a qualified engineer.

Sources

  1. 1.2025 Publications Catalog (entries for Std 650, Std 653, Std 625, RP 651 and RP 652) (API Std 650, 13th edition, March 2020, with Errata 1 (January 2021); API Std 653, 5th edition, November 2014, with Addenda 1 and 2) · American Petroleum Institute (API)
  2. 2.API Standard 650: 13th Edition (standards news) · American Petroleum Institute (API)
  3. 3.Investigation Report: Allied Terminals, Inc., Catastrophic Tank Collapse (Report No. 2009-03-I-VA) · US Chemical Safety and Hazard Investigation Board (CSB)
  4. 4.Chemical Safety Alert: Rupture Hazard from Liquid Storage Tanks (EPA 550-F-09-004) · US Environmental Protection Agency (EPA)
  5. 5.49 CFR 195.3, What documents are incorporated by reference partly or wholly in this part? · eCFR, US Office of the Federal Register
  6. 6.49 CFR 195.132, Design and construction of aboveground breakout tanks · eCFR, US Office of the Federal Register
  7. 7.49 CFR 195.205, Repair, alteration and reconstruction of aboveground breakout tanks, and 195.432, Inspection of in-service breakout tanks · eCFR, US Office of the Federal Register
  8. 8.49 CFR 195.307, Pressure testing aboveground breakout tanks · eCFR, US Office of the Federal Register
  9. 9.49 CFR 195.565, How do I install cathodic protection on breakout tanks?, and 195.579, What must I do to mitigate internal corrosion? · eCFR, US Office of the Federal Register
  10. 10.29 CFR 1910.106, Flammable liquids · eCFR, US Office of the Federal Register
  11. 11.NIST Special Publication 780, Guidelines for Pressure Vessel Safety Assessment (S. Yukawa) · US National Institute of Standards and Technology (NIST)